1 2 3 4 5 6 7 8 9 10 11 .. 71
Outdoor Unit • VRV Classic • RXYCQ-A
1
2
VRV Systems • Outdoor Unit
4
2
Specifications
Standard Accessories : Connection pipes; Quantity : 4;
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Refrigerant
Type
R-410A
Charge
kg
6.2
7.7
8.4
8.6
11.3
11.5
11.7
Control
Electronic expansion valve
Circuits
Quantity
1
Refrigerant oil
Type
Synthetic (ether) oil
Charged volume
l
1.7
2.6
4.5
4.8
7.0
7.1
Piping connections
Liquid
Type
Braze connection
OD
mm
9.52
12.7
15.9
Gas
Type
Braze connection
OD
mm
15.9
19.1
22.2
28.6
Heat insulation
Both liquid and gas pipes
Piping length
OU - IU
Max.
m
135
After
branch
Max.
m
90 (7)
Total piping length
System
Actual
m
300
Level difference
OU - IU
Outdoo
r unit in
highest
position
m
3
0
Indoor
unit in
highest
position
m
-
IU - IU
Max.
m
15
Defrost method
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan driver overload protector
03
Overcurrent relay
04
Inverter overload protector
05
PC board fuse
PED
Category
Category II
2-1
Technical Specifications
RXYCQ8A
RXYCQ10A
RXYCQ12A
RXYCQ14A
RXYCQ16A
RXYCQ18A
RXYCQ20A